- Mains supply: 230V 50/60Hz.
- Mains rated current: 810mA max.
- Internal power supply: 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
- Total output current limited to: 1.5A @ 230Vac continuous, 3A peak (ImaxA eq 800mA).
- Quiescent current: 40mA (on mains fail). Zone quiescent 2mA max.
- Max battery size and type: 2 x 12V 7Ah VRLA connected in series.
- No. of detector zone circuits: 3 @ 19-28Vdc (Max. length per circuit is 250m).
- Max. devices per detector zone: 20 detectors (or 32 detectors/manual call points combined).
- No. of conventional sounder circuits: 3 (two x 1st stage; one x 2nd stage). Max. length per circuit is 50m).
- EOL resistor value: 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
- Max. sounder output current: 3 x 200mA.
- Auxiliary relays: Six: (1) Fire;
(2) Local Fire;
(3) Extract Fan;
(4) 1st Stage;
(5) 2nd Stage;
(6) Fault. Volt free single pole changeover. Max. switch current 1A;
Max. switch voltage 30Vdc. Five additional relays
- Other outputs: Extinguishant release (21-28Vdc, rated at 1A for 5 mins).
Programmable to delay by 0-60 seconds;
to be active for 1-300 seconds and to flood for 60-1800 seconds.
- Auxiliary inputs: Six: (1) Manual Release;
(2) Flow Switch;
(3) Low Pressure;
(4) Mode;
(5) Hold;
(6) Abort. 8K-2KΩ normal;
1.8K-200Ω active;
150-0Ω short circuit.
EOL value: 6K8 +/-5%, 0.25W.
- Indicators: Multiple indicators are provided – refer to the EP203 instructions for details.
- Expansion connections: Yes – for up to 8 x Remote status units (2 wire RS485 + 2 wire power)
and/or up to 8 x Ecomomy status units (2 wire power + 2 wire mode select).
- Product dimensions (mm): 439 W x 276 H x 70 D mm (back box); 467 W x 293 H x 29 D mm (lid).
- Construction & finish: Metal back box; metal chassis' plastic lid.
- IP Rating: IP30.
- Weight: 4.2kg (without batteries).
- Operating conditions/temperature: -5ºC to +40ºC. Max relative humidity: 95%.
- Mains supply: 230V 50/60Hz.
- Mains rated current: 700mA max.
- Internal power supply: 27V nominal.
- Total output current limited to : 3A @ 230V.
- Quiescent current: 90mA
- Max battery size and type: 2 x 12V 7Ah VRLA connected in series.
- No. of detector zone circuits: 16 (Max. length per circuit is 500m).
Can be extended to 28 zones using FF501Z 4 Zone - extender PCB kits.
- Call point resistor value: 470 to 680Ω.
- Max. devices per detector zone: 20 detectors (max. detector current 2mA).
- No. of conventional sounder circuits: 4 (Max. length per circuit is 500m).
- EOL resistor value: 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
- Max. sounder output current: 3mA (to all outputs). Outputs are fused at 1A.
- Auxiliary relays : 1 x onboard relay (1A, 30 VDC, follows sounders).
- Open collector outputs: 2 x Fire and 1 x Fault output available via optional FF574X expansion loom. Max. sink current 100mA.
- Auxiliary inputs: Class change input available via optional FF574X expansion loom.
- Indicators: Mains On;
Gen Fire;
Zone Fire;
Zone Fault (S/C, O/C, head out, Zone disabled);
Sndr Fault;
Processor Fault;
Batt/PSU Fault;
Aux O/Ps Disabled;
Fault Sounder (fault, silenced fire and delayed sndrs)
- Controls: External (key operated): Reset/Test Scroll;
Silence Alarm/Fault Sounders;
Evacuate;
Disable. Internal: OMT;
Sounder Walk Test;
Sounder Isolate;
Sounder Delay;
S/C equals fire;
Non-latching zones.
- Product dimensions (mm): 521 W x 334 H x D 140mm.
- Construction & finish: Metal lid and base.
- IP Rating: IP30.
- Weight: 9.5kg.
- Operating conditions/temperature: -5ºC to +40ºC. Max relative humidity: 95%.
- Quiescent current: 0mA (none).
- Alarm current: Determined by the type of control equipment and
- number / type of field devices connected to the system.
- Controls: Green button.
- Product dimensions (mm): 87 H x 87 W x 58 D mm. Surface or flush mounting.
- Construction & finish: Polycarbonate. Green push button, yellow call point housing, black back box.
- IP Rating: IP24.
- Weight: TBC
- Operating conditions/temperature: -0ºC to +65ºC. Max. relative humidity 95% non-condensing
- Connection Details: See Instruction manual
- Cable Termination: 0.5-2.5mm2
- Maximum Voltage: 30VDC
- Current Rating (switch only): 2 Amps
- Humidity: 93± 3% non-condensing
- Operating Temperature: -100C to +550C
- Storage Temperature: -100C to +550C
- Ingress Protection (IP) Rating: IP24D
- Material: Polycarbonate PC/ABS Acrylonitrile Butadiene Styrene
- Weight: 180g
- Colour: Red
- Price mentioned per piece
- Loop-powered addressable combined sounder + beacon
- 103 dB(A) audible alarm output
- Onboard short-circuit isolator
- 7 volume settings + 15 tone pairs
- 550 µA standby current
- Deep base form factor
- Available IP55 weatherproof variant
- Price mentioned per siren
- Model No: CP450SER (Sounder/Beacon)
- Output @ 1 metre 24VDC: 68 dB 95 dB
- Current @ 24VDC: 13 mA 22 mA
- Voltage Range: 20 to 28VDC
- Operating Frequency: 800Hz to 1000Hz
- Number of Tones: 4
- Volume Control: Adjustment Screw
- Operating Temperatures: -20°C to +70°C
- Protection Classification: IP 65
- Price mentioned per piece